Motor Protection RelayMODEL : µeLEDX-T7 Segment LED/4 Digit Display Protection Over Load Single Phasing Unbalance Under Current Lock Rotor Short Circuit High and Low Voltage Earth Leakage (Extra CBCT Required) Features A, V, KW, Kwh & PF Display Hour Counter Start Counter Start Counter RS - 485 Communication Modbus Protocol I-T Characteristic Fault Annunciation display type of fault Last 5 Fault History FIFO based Dimension: 96 x 96 mm, Flush Mounting Optional Features Analog O/P (4-20mA/ 0-10VDC) Password Protection RTC Extra Relay Output LCD Display Product Range 0.2 - 12.5 Amp, With External Line CTs -03 Nos. ID - 20mm 0.8 - 25 Amp, With External Line CTs -03 Nos. ID - 20mm 2 - 62.5 Amp, With External Line CTs -03 Nos. ID - 20mm 4 - 125 Amp, With External Line CTs -03 Nos. ID - 35mm 40 - 250 Amp, With External Line CTs -03 Nos. ID - 55mm 80 - 500 Amp, With External Line CTs -03 Nos. ID - 55mm* *Note: Current range 80-500 Amp is available with all the above protections except short circuit protection. Download